| Ratedvoltage |
230 / 115 / 42V AC; 24V AC/DC |
| Voltagerange |
0,8 to 1,1 x rated voltage |
| Frequencyrange |
50 / 60 Hz |
| Powerconsumption |
approx. 3,5 VA |
| Ratedinsulationvoltage |
250 V |
| Surface-leakagepathsandairgaps |
Overvoltage category III Pollution level 2 to DIN VDE 0110-1 (01/89) and DIN VDE 0110-2 (01/89) |
| Testvoltage |
2,5k V |
| Ambienttemperature |
-5°C to +55°C |
| Modeofprotection |
IP 20 terminals, IP 40 casing to DIN VDE 0470-1 (11/92) |
| Switchingcapacity |
250 V AC; 5 A; 1200 VA /120 W 24 V DC preferably with spark arrest |
| Utilisationcategory |
AC-15, DC-13 |
| Responsetime |
on:approx. 170 ms; off approx. 15 ms |
| Outputcontacts |
3 N/O (safety contacts) 1 N/C (auxiliary contact) |
| Mechanicalservicelife |
107 schwitching cycles |
| Switchmaterial |
AgSnO, 0,5ľ Au |
| Terminalbolts |
Termina lbox with wire protection |
| Linecrosssection |
rigid 4mm2, flexible2.5mm2, connectin glead to bestripped up to max.4mm |
| Controlcircuit |
approx.24VDC |
| Outputcontactfuse |
6A slow blow |
Models and Ordering Data:
Type |
|
Order No. |
F101 |
230VAC |
074 00001* |
F101 |
115VAC |
074 00002 |
F101 |
42VAC |
074 00003 |
F101 |
24VAC / DC |
074 00004* |
| *) Approval for U.S. / Canada |
|
Function Diagram:
|
Dimension Drawing:
|
|