Ratedvoltage |
230 / 115 / 42V AC; 24V AC/DC |
Voltagerange |
0,8 to 1,1 x rated voltage |
Frequencyrange |
50 / 60 Hz |
Powerconsumption |
approx. 3,5 VA |
Ratedinsulationvoltage |
250 V |
Surface-leakagepathsandairgaps |
Overvoltage category III Pollution level 2 to DIN VDE 0110-1 (01/89) and DIN VDE 0110-2 (01/89) |
Testvoltage |
2,5k V |
Ambienttemperature |
-5°C to +55°C |
Modeofprotection |
IP 20 terminals, IP 40 casing to DIN VDE 0470-1 (11/92) |
Switchingcapacity |
250 V AC; 5 A; 1200 VA /120 W 24 V DC preferably with spark arrest |
Utilisationcategory |
AC-15, DC-13 |
Responsetime |
on:approx. 170 ms; off approx. 15 ms |
Outputcontacts |
3 N/O (safety contacts) 1 N/C (auxiliary contact) |
Mechanicalservicelife |
107 schwitching cycles |
Switchmaterial |
AgSnO, 0,5ľ Au |
Terminalbolts |
Termina lbox with wire protection |
Linecrosssection |
rigid 4mm2, flexible2.5mm2, connectin glead to bestripped up to max.4mm |
Controlcircuit |
approx.24VDC |
Outputcontactfuse |
6A slow blow |
Models and Ordering Data:
Type |
|
Order No. |
F101 |
230VAC |
074 00001* |
F101 |
115VAC |
074 00002 |
F101 |
42VAC |
074 00003 |
F101 |
24VAC / DC |
074 00004* |
*) Approval for U.S. / Canada |
Function Diagram:
|
Dimension Drawing:
|
|